Communications configuring
3-150
System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003
•
If you have configured, using virtual connections,
more data
than
specified at connection LTT of function block @PEER, then this
excess data is
cut-off.
•
If you have configured, using virtual connections,
less data
, than are
specified at the LTT connection of function block @PEER, then the
telegram is
filled-up
with
"0s".
•
The transmit telegram is started
synchronously to the sampling time
of
the CTV function block, i.e. there is no dead time.
Please refer to the "Manual, configuring the communications D7-SYS,
Chapter communications utility, process data" for additional configuring
rules for exchanging process data.
Number of process
data, each 16 bit
Baud rate [kbaud]
9.6
19,2
38,4
93,75
187,5
1 5.7
2.9
1.43
0.6
0.3
2 8.0
4.0
2.0
0.8
0.4
5 16
8.0
4.0
1.6
0.8
Table 3-58
Telegram run times [ms] as a function of the baud rate and the number of process data
3.15.2.2 Receiving
You must configure the
CRV function block
so that you can receive
process data.
Select the "refresh" data transfer mode, i.e. you always have access to
the most up to date data.
Configure a unique channel name for this interface at connection AR.
•
If you have configured, using virtual connections,
more data
than
specified at connection LTR of function block @PEER, then this
excess data is
cut-off.
•
If you have configured, using virtual connections,
less data
, than are
specified at the LTR connection of function block @PEER, then the
telegram is
filled-up
with
"0s".
•
The transmit telegram is started a
synchronously to the sampling time
of the CRV function block after a telegram has been received, i.e. the
sampling time of function block CRV is the max. deadtime between
receiving and processing data.
Please refer to the "Manual, configuring the communications D7-SYS,
Chapter communications utility, process data" for additional configuring
rules when transferring process data.
Please observe:
Please observe: