Communications configuring
3-120
System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003
Communications reference
:
2
Type
:
Non-cyclic client
Association type
:
MMAZ
Local
LSAP
:
10
Remote address
:
2
Remote
LSAP
:
12
Max. PDU length
:
241
Monitoring
interval
:
0 s
Password :
0
Group
:
0
Profile :
0
Supported utilities
:
Read :
No
Write
:
.req
Get OV (detailed version)
:
.req
Information
report
:
No
Symbolic
addressing
:
.req
Max. number of parallel tasks:
Transmitting :
1
Receiving
:
0
Name :
CLI WRITE 2
Table 3-54
Mask, "Non-cyclic client"
Explanations:
•
Station 1 is the client so that the "Non-cyclic client" mask is selected
here.
•
"Communications reference" 2 corresponds to the data entry made in
address stage 1 at input AT of the SIMADYN D transmit block.
•
The "Association type" is non-cyclic, master-master, as both stations
(SIMADYN D) are master.
•
"Local LSAP", "Remote address" and "Remote LSAP" define the
communications path between the two stations.
•
The default values were used for the fields "Max. PDU length",
"Monitoring interval", "Password", "Group", "Profile".
•
The "Get OV (detailed version)" and "Write" utilities are supported and
more specifically as requester. A client is always a requester as far as
this utility is concerned.
−
"Write" must be supported, because the transmit function block is
appropriately configured.
Station 1,
communication
association 2: