Communications configuring
3-56
System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003
•
The diagnostics data is dependent on the slave type.
•
The first 16-byte slave diagnostic data are output.
•
Additional slave diagnostic data can be output with SEL>1000.
Further information
on slave-specific diagnostics data, refer to the user documentation
"COM PROFIBUS" and the User Documentation for the individual
PROFIBUS slaves.
Slave type
SPC slaves,
general
ET 200U ET 200B
ET 200K
SPM
slave
ET 200C
8DE/8DA
DP
stand.
slaves
Connection
D01 low
Status
1
Diagnostics
high
Status
2
according
to the
standard
D02
low
Status 3
6 bytes
high
Master PROFIBUS address
D03
low
Identification number, high byte
high
Identification number, low byte
D04
low
Header, device-related diagnostics
high Device
diagnostics
U Device
diagnos. B
0 0 0
D05 low Header
identification-
related diagnostics
0 0 0 0
high
BG 7-0
0
Channel 7-0
D06
low
BG 15-8
0
Channel 15-8
0
Device-
high
BG 23-16
0
Channel 23-16
0
specific
D07
low
BG 31-24
0
Channel 31-24
0
diagnostics
high Additional
device-
Irrelevant
D08 low
specific
Irrelevant
high
diagnostics
Irrelevant
Table 3-25
Overview of the structure of the diagnostics data for Siemens DP slaves
Diagnostics data of
SIEMENS DP
slaves