S&C Instruction Sheet 1043-550
67
Status Point Description
Category
Explanation
Not all teams xfer rdy (513)
IntelliTEAM
Active if any teams where the local control
is a member are not fully operational. This
may be due to error conditions at individual
team members (see Switch not xfer rdy),
or team wide conditions such as isolation
of a fault, team configuration errors, team
coordination errors, automatic restoration
prohibited, and team logic disabled on the
TEAM: Setup screen. If Switch not xfer rdy
is active in one switch control of a team,
this will cause this indication to be set in
the other team members.
RT-Load Data Problem (522) IntelliTEAM
This point is set when the DNP analog out-
put value received is less than the real-time
3-phase total load as reported by the host
device, and is also set if the real-time feeder
loading data has not updated within the
configured time interval. This point will be
set to 0 if the real-time feeder loading logic
is inactive.
RTN in progress (515)
IntelliTEAM
Active while the team is returning the cir-
cuit to its normal configuration.
SCADA Prohibit Rest. (516)
IntelliTEAM
Active when a SCADA command was
received to prevent the restoration of any
load by this team member. Will also be
activated when Prohibit Restoration is
requested via IntelliLINK or the Keypad.
Setup Data Revision (518)
IntelliTEAM
Active when the configuration data for an
enabled team has been modified. It remains
active until the field is disabled and then
re-enabled. You can clear this error in two
ways: 1. Set the Team Setup setpoint (on
the SETUP: Team screen) to Stopped,
then set it to Running. 2. Reload the team
configuration data using the IntelliLINK
software. Select File > Load Setpoints. This
process automatically stops and restarts the
“Team Setup” setpoint.
Src. Loading Data Active
(521)
IntelliTEAM
This point will be set when the real-time
feeder loading logic is active and in use.
This point does not indicate whether the
control is using actual real-time feeder load-
ing data received from a DNP master, or
using the Default Source Segment Loading
setting.
Data Logging