42 S&C Instruction Sheet 1043-550
Category
Event Description
Definition
Log Level
DNP
Serial port reset error (Port
Number 1 [1=port a, 2=port B,
3=port C, 4=port D])
An error occurred in reset of a serial port during a
communications setpoint configuration change. Changes to
serial port configuration may not have taken affect.
Normal
DNP
Analog output code not mapped
(Point Code, Associated RTU
Address, N/A, N/A)
An analog output point special function was not added to the
list because the analog output point is not yet included in the
point mapping configuration.
Extended
DNP
Analog output function registered
(Point Code, Associated RTU
Address, N/A, N/A)
An analog output point special function was successfully added
to the list. This function connects an analog output operation
with functionality elsewhere in the application.
Extended
DNP
Bad amount of data received
(Source Address, Reported
Length, Actual Length, N/A)
The application layer detected an inconsistency in the amount
of data in the fragment. The fragment was discarded.
Extended
DNP
Bad fragment length received
(Fragment Length, N/A, N/A,
N/A)
The application layer detected a fragment with an invalid
length. The valid rand is from 2 to 2048 bytes. The fragment
was discarded.
Extended
DNP
Bad frame length (Actual Length,
Indicated Length, N/A, Code
Location)
The actual length of the received DNP frame does not match
the length indicated in the DNP data link header. The frame is
discarded.
Extended
DNP
Bad object range index (Source
Address, First Index or Index
Size, Last Index or Qualifier,
Code Location)
An error was detected in an object header of the current request
message related to the data index values. An attempt will be
made to process other objects within the message.
Extended
DNP
Bad transmit fragment length
(Fragment Length, N/A, N/A,
N/A)
The application layer was requested to send a fragment larger
than the 2k size limitation.
Extended
DNP
Bad transport segment length
(Segment Length, N/A, N/A, N/A)
The transport segment length of the DNP frame is invalid. The
frame was discarded. The valid range is from 3 to 250.
Extended
DNP
Control point code not mapped
(Point Code, Associated RTU
Address, N/A, N/A)
A control point special function was not added to the list
because the control point is not yet included in the point
mapping configuration.
Extended
DNP
Control point function registered
(Point Code, Associated RTU
Address, N/A, N/A)
A control point special function was successfully added to
the list. This function connects a control operation with
functionality elsewhere in the application.
Extended
Data Logging