S&C Instruction Sheet 1043-550
23
Internal Error
This field reads
None
when no internal errors are present in a team member. Possible
error values are:
Trouble
The switch is disabled because of a bad battery or other
condition.
NotAuto
The switch has been placed into a non-automatic condi-
tion.
ManOR
The switch’s open/close state has been manually overridden
by either a faceplate or SCADA operation.
No Op
The switch has detected an error in operation following a
transfer event. A close or open operation was requested, but
either the team member was unable to perform the operation,
or the switch tripped back open based on shots-to-lockout
logic (close request only).
NOTE:
ManOR
and
No Op
status can be cleared on the
PRESENT CONDITIONS
screen using the
Clear Manual
Switch Operations
Clear
command. They can also be
cleared on the
Team Sw. Errors
screen of the LCD, or with
a SCADA command.
ProRes
The switch has been sent a Prohibit Restoration com-
mand.
Event Status
This is the present status of events related to this team member. The field can include a
combination of possible values:
O
Latched overcurrent event.
V
Latched voltage loss, any or all phases
P
Latched phase loss sectionalizing event
Vr
Real-time voltage loss, any phase
3Vr
3-phase real-time voltage loss
Avg Load
This is the
2-minute averaged
3-phase load reported by each individual team member.
This value is used when determining the
Local Real-Time Load
. Following a circuit event,
this value is frozen at the last value reported before the event began; this insures that the
team uses pre-event values during the transfer. The value is not updated until after the
transfer.
Rev Current
This field reads
Active
when a team member senses reverse current.
Team Problems