S&C Instruction Sheet 1043-550
71
Status Point Description
Category
Explanation
Reclose Mismatch (341)
UIM
Active when the Interface Module has
detected that the state of the host’s
Reclosing feature is no longer in the
expected state. The Interface Module
assumes this change of state is due to
human intervention and will force a Stop
Transfer condition, preventing IntelliTEAM
II from attempting to operate the relay/
recloser device.
Recloser Cycling (347)
UIM
Active when the recloser/relay is pro-
grammed for fault cycling and fault cycling
is active.
Recloser Cycling Reset (348) UIM
Active when the recloser/relay is pro-
grammed for fault cycling and reset state is
entered.
Remote Disabled (338)
UIM
Active when the host relay/recloser device
indicates it is not able to accept commands
from a remote source. The remote source
can be either SCADA or the Interface Mod-
ule itself.
Single Phase Trip (350)
UIM
Active when UIM is programmed to do
extended phase loss protection and the
switch trips for that reason. Cleared on any
close operation.
Three Phase Trip (351)
UIM
Active when UIM is programmed to do
extended three phase voltage loss pro-
tection and switch trips for that reason.
Cleared on any close operation.
Tripped to Lockout (346)
UIM
Active when the UIM has detected that the
external device has tripped to the lockout
state as a result of an event. Once in the
lockout state IntelliTEAM II may begin the
reconfiguration process.
Data Logging