S&C Instruction Sheet 1043-550
63
Category
Event Description
Definition
Log Level
UIM
Profile mismatch error
If the normal profile is supported and the reported status
doesn’t match, a 30-second timer is started to see if
IntelliTEAM is trying to change the profile. If the timer expires
without a detected change, a mismatch error is sent.
All
UIM
Protection settings-mapped pts
mismatch
When protection settings are enabled in SETUP: Automatic
Operation and associated control, analog and status points
are not mapped in the UIM. When BEGIN SETUP is set
to
Running
a check is made for the mapped points and a
mismatch condition is entered causing a not ready team alarm.
When the points are not correct and going to Running has
found an error, this message is output.
All
UIM
Protection settings-mapped pts
OK
When protection settings are enabled in SETUP: Automatic
Operation and associated control, analog and status points
are not mapped in the UIM. When BEGIN SETUP is set
to
Running
a check is made for the mapped points and a
mismatch condition is entered causing a not ready team alarm.
When the points are correct and going to Running finds no
errors, this message is output.
All
UIM
Recloser blocked timer expired
After the UIM has verified a close operation, IntelliTEAM will
wait an additional amount of time specified at: External Device
Menu, SETUP: Automatic Operation, Recloser Block Time.
All
UIM
Recloser/relay is fault cycling
If the recloser/relay is programmed for fault cycling, this
message is output when fault cycling is active.
All
UIM
Recloser/relay is in reset state
If the recloser/relay is programmed for fault cycling, this
message is output when a reset state is entered.
All
UIM
Recloser/relay not in reset state
The UIM has detected that the external device status is no
longer in reset.
All
UIM
Reclosing mismatch cleared
The UIM had detected an unexpected mismatch in Reclosing
setting between the present state of the external device and
the state as configured in the SETUP: Automatic Operation
screen. The mismatch has been cleared and will not prevent the
associated team from being Ready.
All
UIM
Reclosing mismatch detected
The UIM has detected an unexpected mismatch in Reclosing
setting between the present state of the external device and the
state as configured in the SETUP: Automatic Operation screen.
Until cleared this mismatch will prevent the associated team
from being Ready.
All
Data Logging