S&C Instruction Sheet 1043-550
59
Category
Event Description
Definition
Log Level
IntelliTEAM
Volt/fault VL cleared (Team, Rec)
The coach clears a 3 phase voltage loss when: 3 phase voltage
loss was previously detected and real time 3 phase voltage is
now present and either the external device is in its normal state
or the external device’s normal job is a source sub. For details
on Rec 2, contact S&C.
All
IntelliTEAM
Xfer State Change (Team)
The transfer state changed for the specified team.
All
LOG
Compact flash card not found
Compact Flash logging Setpoint is on but either no CF card is
inserted or the card is not formatted correctly. The only way to
fix this is to insert a working CF card.
Normal
LOG
Compact flash card swap detected
The application determined that the compact flash card has
been swapped.
Normal
LOG
Compact flash data likely lost on
err
A Compact Flash operation was interrupted before completion.
The file on which this occurred was saved with a .ERR
extension and abandoned. Some events may have been lost
from the CF log. The primary reason for this condition is a
loss of power while CF card is active - a highly improbable but
possible event. Another reason is that the card was pulled out
while data was being written to it. This is why it is necessary
to disable CF logging either through the IntelliLINK screen, or
the faceplate keypad before removing the card. Notify S&C if
you see this message more than a few times.
Normal
LOG
CF buffer processed early to
preserve data
The application tries to access the CF every several seconds
at a fixed time interval to increase overall application
performance. However, if the volume of event data is such that
the interval is not soon enough, logging events are saved to the
CF card more frequently, which is what this message means.
This message does not indicate any loss of event data and is to
be expected during heavy team activity.
All
LOG
Compact flash operation failed
A CF disk error occurred while saving logs to the CF card.
There may be many reasons for this, but errors seldom occur.
If this message occurs persistently, replace the CF card to
ensure continued logging, and notify S&C.
All
LOG
DNP error
Logging could not communicate to DNP.
All
LOG
Logging overflow (Last Events)
A large but not infinite number of events can be logged per
unit of time. This message is displayed when this limit is
reached or exceeded. The internal identification of last events
is supplied in the data columns, and is diagnostic information
for S&C. Data is seldom lost, but this message may indicate
data loss. If you see this message often, please contact S&C.
All
Data Logging