22 S&C Instruction Sheet 1043-550
Present State
This is the present position of each switch in the team:
Open
The switch is open.
Closed
The switch is closed.
----
The switch state is unknown, or the record is not in use. This
is the initial state of all switches and is considered an error
condition during normal operation.
Auto Mode
This field shows the automatic features enabled for each team member. You entered this
information for each team member on the
SETUP: Automatic Operation
and
SETUP:
Team
screens. It also indicated whether the switch control has been temporarily placed
in manual operation mode. The field can include a combination of possible values:
M
The switch control has been temporarily placed in manual
mode via the faceplate or SCADA command.
A
Automatic sectionalizing has been enabled with the features
configured on the
SETUP: Automatic Operation
screen.
V
Sectionalizing on loss-of-voltage only is enabled.
T
Automatic transfer logic has been enabled on the
SETUP:
Team
screen.
Ro
Return-to-Normal logic using an open transition has been
enabled on the
SETUP: Team
screen.
Rc
Return-to-Normal logic using a closed transition has been
enabled on the
SETUP: Team
screen.
Team Problems