66 S&C Instruction Sheet 1043-550
Status
ACTIVE means that the condition which this status point represents is active right now;
while INACTIVE means that the condition which this point represents is not active right
now.
Total Cnt
How many times the status point has been active since the application was downloaded
first.
Current Cnt
How many times the status point has been active since status points were reset last time
(either using the “Clear Status Counters” feature on the Logging Setup screen, or the
identical feature in the lower right corner of this screen).
Time Active
At what time the status last became active. This is cleared together with “Current Cnt” by
the user, when the “Clear Status Counters” feature is used.
Time Cleared
At what time the status was cleared last. This is cleared together with “Current Cnt” by
the user, when the “Clear Status Counters” feature is used.
In addition to showing the status table, the screens allow to clear status point counters
and timestamps and show the time of last status clearing. That functionality is available
in the lower portion of the
Logging Status Point
screen and is also found on the
Data
Logging Setup
screen.
Here is the list of status points currently supported by the UIM. The number in parenthe-
sis is the internal point code, that needs to be supplied in the appropriate DNP mapping
screen to make the point accessible to SCADA.
Status Point Description
Category
Explanation
Err get local sw. data (519)
IntelliTEAM
Active when IntelliTEAM fails to receive all
data necessary for its operation from the
external device.
Manual Op. Team Condition
(520)
IntelliTEAM
Active if any team registered a manual
switch operation (Open or Close) such
that it became
not
fully operational. Some
manual operations will not cause this condi-
tion, most notably closing a source switch
on a previously faulted team to allow TRN
(if RTN is enabled) to take place.
Data Logging