60 S&C Instruction Sheet 1043-550
Category
Event Description
Definition
Log Level
UIM
Any phase overcurrent cleared
The external device reports that an overcurrent condition has
been cleared on one or more phases.
All
UIM
Any phase voltage loss cleared
The external device reports that a voltage loss condition has
been cleared on one or more phases.
All
UIM
Automatic operation enabled
The external device reports that automatic operation is enabled.
All
UIM
Communication lost to E.D.
cleared
When the external device (E.D.) starts communicating again,
this message is output.
All
UIM
Communication to E.D. lost
When the external device (E.D.) stops communicating, for
example a radio problem, this message is output.
All
UIM
Communication to E.D. running
When BEGIN SETUP is set to Running this message is output.
All
UIM
Communication to E.D. stopped
When BEGIN SETUP is set to Stopped this message is output.
All
UIM
Control device voltage loss
cleared
The UIM has detected the external device report that voltage
has returned to the source side.
All
UIM
Control point operation req.
The UIM is issuing a control request on behalf of IntelliTEAM
II to the external device. Data 1 indicates the control point
being operated. The codes have the following meaning:
1 = Close
2 = Trip (Open)
60 = Normal Profile (settings group 1)
61 = Alternate Profile 1 (settings group 2)
62 = Alternate Profile 2 (settings group 3)
63 = Alternate Profile 3 (settings group 4)
58 = Alternate Profile 4 (settings group 5)
59 = Alternate Profile 5 (settings group 6)
64 = Reclosing Block
65 = Ground Trip Block
66 = Hot Line Tag
All
UIM
Control profile enabled
If the normal profile is supported and the reported status does
match, any previous mismatch errors are cleared and this
message is output.
All
Data Logging