62 S&C Instruction Sheet 1043-550
Category
Event Description
Definition
Log Level
UIM
Ext VLoss/PLoss qual-Sw already
open
When extended phase or three phase voltage losses are
qualified and the reported switch status is open, this message
is output.
All
UIM
Fault cycling state cleared
The UIM has detected that the external device fault cycling
status has cleared.
All
UIM
Frequency trip active
The UIM has detected that the external device had tripped open
due to a frequency anomaly.
All
UIM
Frequency trip cleared
The UIM has detected that the external device had tripped open
due to a frequency anomaly, and that the frequency condition
has cleared.
All
UIM
Frequency trip inactive
The UIM has detected that the external device has not tripped
open due to a frequency anomaly.
All
UIM
Ground trip mismatch cleared
The UIM had detected a mismatch in Ground Trip setting
between the present state of the external device and the state
as configured in the SETUP: Automatic Operation screen.
The mismatch is now cleared, and the associated team is not
prevented from being Ready.
All
UIM
Ground trip mismatch detected
The UIM has detected an unexpected mismatch in Ground Trip
setting between the present state of the external device and the
state as configured in the SETUP: Automatic Operation screen.
Until cleared this mismatch will prevent the associated team
from being Ready.
All
UIM
Hot line tag active
The UIM has detected that the Hot Line tag feature of the
external device is active.
All
UIM
Hot line tag inactive
The UIM has detected that the Hot Line Tag feature of the
external device is inactive.
All
UIM
IntelliTEAM disabled extended
PL/Vloss
When teams go out of ready, IntelliTEAM will signal the UIM
to disable extended loss of voltage operation, if the UIM is
programmed for this operation.
All
UIM
IntelliTEAM enabled extended
PL/Vloss
When teams are ready, IntelliTEAM will signal the UIM
to enable extended loss of voltage operation, if the UIM is
programmed for this operation.
All
UIM
Open on extended PL or VL failed
When the UIM sends the command to open on extended phase
or 3 phase voltage losses and the switch status doesn’t change,
this message is generated.
All