S&C Instruction Sheet 1043-550
9
D. Check for error messages on the HISTORIC EVENT VIEW screen. To perform this
check, connect directly to the faceplate communications port and select “ICP” in
the IntelliLINK Communications Setup dialog box. See “HISTORIC EVENT VIEW
Screen” on page 35 for more details.
SCADA commands are ignored by the Interface Module/Host control device
A.
Check for Interface Module power
.
B.
Check the RTU address
. At the
SETUP: Communications
screen, check
which
Communications RTU Address
is used by this switch control. Make sure
the SCADA master station is sending commands for this control to the correct
address.
C. Check your communications hardware. See the manufacturer’s documentation
for details.
The
LOCAL OPERATION, TEAM OPERATION
, and
TROUBLESHOOTING
screens
can help you check the present status of:
• this Universal Interface Module
• other team members
• team
operations
These screens can also help you locate the cause of various team and team member
problems.
Using IntelliLINK to
Locate Problems
Troubleshooting Problems