S&C Instruction Sheet 1043-550
53
Category
Event Description
Definition
Log Level
IntelliTEAM
Software mismatch on arriving
coach
There is a software revision incompatibility within the team.
The data fields show revision and version information for the
team member from which the coach just arrived.
Normal
IntelliTEAM
Sw opened for xfer (Team, Rec)
During a transfer event, the coach of the specified team opened
the switch indicated to allow the transfer operation to continue.
This may occur when one or more switches within the team are
not coordinated to open at the same time as the other switches.
Normal
IntelliTEAM
Switch is xfer ready
The local switch on the specified team is ready for transfer
operations.
Normal
IntelliTEAM
Switch not xfr ready
The local switch on the specified team is not ready for transfer
operations. This may be caused by an internal switch error (for
example, a bad battery).
Normal
IntelliTEAM
Switch open fail (Team, Sw)
The specified team was unable to open the switch/position
indicated.
Normal
IntelliTEAM
Switch open ok (Team, Sw)
The specified team successfully opened the switch/position
indicated.
Normal
IntelliTEAM
Switch open to break extended
parallel
During a closed transition Return to Normal, the team
member at a tie switch automatically opened the switch after a
prescribed timeout. This insured that a circuit parallel was not
left in place indefinitely. This condition is not normal, and may
have resulted in load being dropped.
Normal
IntelliTEAM
Team Comm Error (Team, RTU)
A team-related message could not be delivered.
Normal
IntelliTEAM
Timer prohibit restoration active
The Prohibit Restoration Timer expired, preventing the
restoration of load by the team for which the timer expired,
however automatic sectionalizing is not affected. If applicable,
this message will also be displayed on power-up.
Normal
IntelliTEAM
Timer prohibit restoration cleared
A SCADA command was received to re-enable the restoration
of load by this team member, and the switch may be closed
automatically. If applicable, this message will also be
displayed on power up.
Normal
IntelliTEAM
Transfer approved (Team, Code)
The transfer operation requested by the specified team,
using the alternate source switch previously determined, was
approved by the adjacent teams. The approval code is also
shown. For details on the code, contact S&C.
Normal
Data Logging