8 S&C Instruction Sheet 1043-550
Team does not reconfigure the circuit
A.
Check the Team Logic setpoint
. Connect your computer to the switch control/
Interface Module and start the IntelliLINK software. On the
SETUP: Team
screen,
check that the
Team Logic
setpoint is enabled for this team.
B.
Check the other
SETUP: Team
screen settings
. Make sure the
DNP/RTU Address
is correct for each team member. Also, check that the normal switch position in the
Normal Open/Close
setpoint is correct for each switch in the team, and that the
normal switch function is correct in the
Normal Sw Func
setpoint. Make sure that
the
Maximum Capacity
settings are appropriate for the circuit conditions.
C.
Check the values on the TEAM OPERATION screen
. Make sure that the Ready
Status reads
READY
. If not, check the
Operational Status, Line Status
, and
Con-
fi guration Status
fi elds for reasons that the team may not be ready.
D.
Check team communications
. See
Team Does Not Communicate
on page 7.
E.
Check the circuit confi guration
. Make sure that the circuit has not been temporar-
ily reconfi gured due to construction or maintenance.
F.
Check whether an event was logged
. Check the
DATA LOGGING HISTORIC
EVENTS
screen to see whether the switch control detected and took action on an
event.
Team does not return the circuit to normal
A.
Check the
Return to Norm Mode
setpoints
. Connect your computer to the
Universal Interface Module and start the IntelliLINK software. On the
SETUP: Team
screen, check that the “Rtn to Norm Mode” setpoint is set properly for this team (Open
or Closed).
B.
Check the present operation mode for each team member
. On the
TEAM
OPERATION
screen, make sure that the
Ready Status
reads
READY
. If not, check
the
Operational Status, Line Status
, and
Confi guration Status
fi elds for reasons
that the team may not be ready.
C.
Check team communications
. See
Team does not communicate
on page 7.
D.
Be sure automatic operation was not disabled
. If automatic operation was dis-
abled at any team member while the circuit was in its reconfi gured state, the Return
to Normal process is canceled.
LCD shows “ALARM” or “FAULT”
Check the TEAM OPERATION screen
. Check the
Operational Status, Line Status
,
and
Confi guration Status
fi elds for the reason(s) that the team is not ready.
DNP communications between PC and team members is not working
A.
Check team communications
. See
Team does not communicate
on page 7.
B.
Check that the DNP cable is connected
. Make sure that the serial cable from your
computer is connected to the cable from the DNP port (usually Port A). Also check
that the DB9 connector is fully seated in the DNP port.
C.
Check the protocol and DNP address being used by the IntelliLINK software
.
Start the IntelliLINK software on your computer. Select Tools > Options > Communi-
cation Setup. Make sure that DNP is the selected protocol. Also check that the Peer
Address matches the “DNP/RTU Address” for the team member with which you are
trying to communicate. Be sure the timeout and the baud rate are set appropriately
as well.
Troubleshooting Problems