50 S&C Instruction Sheet 1043-550
Category
Event Description
Definition
Log Level
IntelliTEAM
Error get local switch data (Team)
An error was detected when the IntelliTEAM II software
retrieved data for the local switch in the specified team. This
may occur if the switch/position number configured on the
SETUP: Team screen is incorrect.
Normal
IntelliTEAM
Error getting all switch data
An error was detected when the IntelliTEAM II software
collected data related to the internal switch function.
Normal
IntelliTEAM
Error put coach task list (Team)
The list of pending tasks that the coach carries between team
members is full in the specified team. No more tasks can be
put on this list until one or more of the existing tasks have been
completed.
Normal
IntelliTEAM
Error put comm task on list
The coach or the team member needs to send a new message to
another team member and the DNP communications buffer is
full. Existing transactions must be completed before more are
put on the communications list.
Normal
IntelliTEAM
Error put event task list (Team)
The list of pending team-related tasks is full in the specified
team. No more tasks can be put on this list until one or more of
the existing tasks have been completed.
Normal
IntelliTEAM
Error put member task list (Team)
The list of pending member-process tasks is full in the
specified team. No more tasks can be put on this list until one
or more of the existing tasks have been completed.
Normal
IntelliTEAM
Event register ok (Team, Task)
The task indicated has enabled event registering for the
specified team. The registering of an event is the process of
making all team members aware that an event has occurred.
Normal
IntelliTEAM
Find alt src result (Team, Rec)
During a transfer event, the team must find an alternate source,
based on the alternate source sequence and the normal function
of the switches within the team (both entered on the SETUP:
Team screen). This message indicates the resulting switch
record, to be used for the team indicated.
Normal
IntelliTEAM
Internal test point
A general internal message to display data that may be
helpful during diagnostics. Please contact S&C if you see this
message.
Normal
IntelliTEAM
Line segment faulted (Team)
The line segment protected by the specified team is the
location of the overcurrent fault on the circuit. The team will
not attempt to restore service to this line segment.
Normal
Data Logging