Pakscan IIE System Manual
68 of 132
Publication S177E V2.0 Issue 03/05
The Up and Down arrow
keys are used to scroll
through the field units
CLEAR - Accept alarms
8.9.4
IQ Analogue Input Field Unit
Analogue input channel 1
A1= 12% FCUTAG01
Tag name
Analogue input channel 2
A2= 34% 1
FCU address
9>Alms=P
Alarms
5>
Block and parameter screen
The IQ actuator can contain two field units, each with their own loop address. The IQ Analogue Input
field unit collects two analogue signals for display and reporting.
The alarms code letters are the same as for an actuator field unit. However, only memory failure (F),
comms failure (C), power on reset (P) and watchdog timer (W) are valid alarms. As with the actuator
page there is a full text display of the alarms that may be found by pressing 9.
Alarms key:
(The letter is present if the alarm has occurred)
F
- FCU memory failure
P
- Power on reset
C
- Communications failure
W
- Watchdog reset
There are no commands associated with this page, though the block and parameter screen does allow
access to the parameters associated with reporting.
Commands available:
-
Go to secondary data page
-
Go to alarm detail page (full text details of field unit alarms)
-
Return to previous menu
MENU
5
CLEAR
9