Pakscan IIE System Manual
42 of 132
Publication S177E V2.0 Issue 03/05
8.7 Diagnostic
Menus
8.7.1
Top Diagnostic Display
Software version
S/W:0124 V5. 8/V5. 2
Port 1 activity
1>Port 1 Rx Tx
Port 2 activity
2>Port 2 Rx Tx
Loop diagnostics
3>Loop 1 x2 >4
Inter-unit comms
The top line shows the code for the software type fitted and its version numbers:
011X
-
single master station
012X
-
hot standby master station
01X1
- 60
channel
unit
01X2
- 120
channel
unit
01X3
- 180
channel
unit
01X4
- 240
channel
unit
(X
means doesn’t matter)
V5.8/V5.2
-
V25 card software version, (5206-014) and loop driver software version,
(5206-034)
The port activity
flags flash to indicate when a message is received (Rx), or when a reply is transmitted
(Tx).
The centre of the fourth line contains a number that indicates loop activity and the field unit that is
currently passing data to the master station (0 or 255 may be shown when no data is being passed),
The message ‘x2’ indicates when the loop is running at double speed. Inter-unit communications
applies to hot standby systems only and is information about the data exchange between the two units
in the hot standby pair.
Commands available:
-
Go to Port 1 diagnostic page
-
Go to Port 2 diagnostic page
-
Go to Loop diagnostic page
-
Go to Inter-unit comms page (hot standby systems only)
-
Return to previous menu
1
2
3
MENU
4