Pakscan IIE System Manual
60 of 132
Publication S177E V2.0 Issue 03/05
8.8.8
ESD Options Setup Menu
ESD Options
1>Serial Disabled
2>Keypad Disabled
3>Input Disabled
This page allows the user to select the ESD (emergency shutdown) function. ESD operation can be
enabled or disabled separately for the serial ports, the keypad, and the hardware input. The default
setting for all three controls is all inputs disabled.
Commands available:
-
Enables / disables host port ESD input
-
Enables / disables keypad ESD input
-
Enables / disables hard wired ESD input, (terminals 32 and 33)
-
Return to previous menu
MENU
1
2
3
Note: A hard wired input ESD will cause a shutdown action when the contact input is open
circuit. The individual actuator function on receipt of the ESD command is set within
the actuator itself. Valves may close, open or stay put during an ESD event.
Once an ESD command has been issued to the actuator field units, local control is
not available until a new command is sent from the master station to each actuator.
The new command may be open, close or stop.