Storage
15 of 132
Publication S177E V2.0 Issue 03/05
3 STORAGE
PROCEDURE
On receipt the hardware should be examined for signs of damage and to ensure that the expected
equipment is present. Identify all the parts.
If the unit is to be stored for a period of time then normal conditions for keeping electronic hardware
must be provided.
The ambient conditions should remain in the following bands at all times:
Temperature:
10 - 30 degrees Centigrade
Humidity:
Not to exceed 80% R.H.
The equipment should not be stacked, though it may be stored in any orientation. The original packing
should be retained.
DO NOT LOSE THE MANUALS.
If it is to be kept for a prolonged period then an electrical exercise test is recommended every 6
months, for 24 hours. The master station internal battery has a shelf life of 3 years.