13 - 12 13 - 12
MELSEC-Q
13 TROUBLESHOOTING
Related buffer memory address
Axis 1 Axis 2 Axis 3 Axis 4 Axis 5 Axis 6 Axis 7 Axis 8
Setting range
Remedy
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Normalize the start request ON timing.
53
153
253
353
453
553
653
753
Cd. 4 Restart request
1: Make restart
•
Do not make a restart request in
"Md. 4 Axis operation status" of other
than "Stopped".
•
Do not make a restart request during
OPR control or JOG operation.
Pr. 5 Speed limit value
6
7
106
107
206
207
306
307
406
407
506
507
606
607
706
707
1 to 200000 (pulse/s)
Pr. 6 Bias speed at start
8
9
108
109
208
209
308
309
408
409
508
509
608
609
708
709
0 to 200000 (pulse/s)
Change the set speed or " Cd. 7 New
speed value" to not less than " Pr. 6 Bias
speed at start" and to not more than
" Pr. 5 Speed limit value".
55
155
255
355
455
555
655
755
Cd. 6 Speed change request
1: Make speed change
Do not make a speed change during
position control or during OPR control.
Refer to "Section 4.5 List of positioning data".
Da. 1 Operation pattern
0: Positioning termination
1: Continuous positioning control
2: Continuous path control
Da. 6 Positioning address/movement
amount
-2147483648 to 2147483647 (pulse)
(For position control)
Correct " Da. 6 Positioning
address/movement amount" or change
" Da. 1 Operation pattern" to "Positioning
termination".
(Refer to Section 9.1.2.)
Summary of Contents for GX Configurator-PT
Page 13: ...MEMO SECTION 1...
Page 127: ...7 20 7 20 MELSEC Q 7 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL MEMO...
Page 129: ...MEMO SECTION 2...
Page 221: ...Index 5 Index 5 MEMO...