13 - 14 13 - 14
MELSEC-Q
13 TROUBLESHOOTING
13.5 Confirming the error definitions using system monitor of GX Developer
Choosing Module's detailed information in the system monitor of GX Developer allows
you to confirm the error code at axis error occurrence.
(1) Operation of GX Developer
Choose [Diagnostics] [System monitor] "QD70 module" and choose
Module's Detailed Information .
(2) Confirmation of error code
The error code stored in "Md. 5 Axis error code" appears in the latest error code
field. (Any of axes 1 to 8)
(By pressing the Error History button, the error code of the error that has
occurred in each axis is displayed in order of axes 1 to 8. Note that this display
does not give a history.)
[Error display details]
Error code of Axis n
Axis n (1 n 8)
[Present Error]
Means error code 103
"Software stroke limit +".
[Display format]
Select "Decimal".
(The error codes indicated in
"Section 13.2 List of errors"
are in decimal.)