4 - 31 4 - 31
MELSEC-Q
4 DATA USED FOR POSITIONING CONTROL
Setting buffer memory address
Item
Setting details
Default
value Axis 1 Axis 2 Axis 3 Axis 4 Axis 5 Axis 6 Axis 7 Axis 8
Cd. 6 Speed
change
request
Set "1" to request speed change processing
(make the " Cd. 7 New speed value" value valid)
after setting " Cd. 7 New speed value" for JOG
operation or speed control of speed-position
switching control.
(The data changes automatically to "0" after
completion of speed change request acceptance.)
0
55
155
255
355
455
555
655
755
Cd. 7 New speed
value
Set the new speed for JOG operation or speed
control of speed-position switching control.
•
Set the value not more than " Pr. 5 Speed limit
value".
•
Set the value not less than " Pr. 6 Bias speed at
start".
[Setting range: 0 to 200000 pulse/s]
0
56
57
156
157
256
257
356
357
456
457
556
557
656
657
756
757
Cd. 8 ACC/DEC
time at
speed
change
Set the time taken at a speed change to reach the
new speed from the old speed.
[Setting range: 0 to 32767ms]
1000
58
158
258
358
458
558
658
758
Cd. 9 DEC/STOP
time at
speed
change
Set the time taken at axis stop factor occurrence
(axis stop signal ON or error occurrence) to make
a stop after reaching " Pr. 6 Bias speed at start"
from the speed after a speed change.
[Setting range: 0 to 32767ms]
1000
59
159
259
359
459
559
659
759