5.7 Simple reciprocating operation
Before operating the system, check the operation of the drive unit.
(Make this check after making sure that the installation, wiring, intelligent function
module switch setting and connection confirmation of the QD70 are normal. For details
of the drive unit, refer to the manual of the drive unit used.)
The following is the way to perform "simple reciprocating operation".
(1) Operation method
Using a sequence program, perform forward run/reverse run of JOG operation.
(Refer to Chapter 10 for details of JOG operation.)
(2) Setting items
Set JOG data in the sequence program. The other data (parameters, positioning
data, etc.) may be initial values.
(Change the JOG data setting values according to the machine specifications.)
Buffer memory addresses
JOG data
Setting value
Setting details
Axis 1 Axis 2 Axis 3 Axis 4 Axis 5 Axis 6 Axis 7 Axis 8
JOG. 1 JOG speed
5000pulse/s
Set the speed for JOG
operation.
40
41
140
141
240
241
340
341
440
441
540
541
640
641
740
741
JOG. 2 JOG ACC time
1000ms
Set the acceleration time
for JOG operation.
42
142
242
342
442
542
642
742
JOG. 3 JOG DEC time
1000ms
Set the deceleration time
for JOG operation.
43
143
243
343
443
543
643
743
JOG. 4 JOG direction flag
0: Forward run JOG
1: Reverse run JOG
Set the rotation direction
for JOG operation.
44
144
244
344
444
544
644
744
Refer to "Section 4.4 List of JOG data" for more information on the setting details.
(3) Reciprocating operation program using JOG operation
The following is a program example for Axis 1.
(When the QD70 is installed in slot 0 of the main base unit)
[Used devices]
Device name
Device
Application
ON details
Remarks
SM400
Normally ON
–
–
Special relay
SM402
ON one scan after RUN
–
–
X0
Module READY
QD70 normal
–
Input
X8
Axis 1 BUSY
Axis 1 running
–
Y0
PLC READY
PLC CPU normal
–
QD70 I/O
Output
Y18
Axis 1 JOG start
Axis JOG starting
–
X28
Forward run JOG
command
Forward run JOG operation
command being given
External input (command)
X29
Reverse run JOG
command
Reverse run JOG operation
command being given
JOG operation is disabled if
X28 and X29 are both ON
or both OFF.
Internal relay
M1
JOG operation flag
JOG operation in progress
–