146
35: During Frequency Output
When the drive is outputting frequency, the assigned output terminal closes.
Terminal
Description
Open
The drive is during stop, baseblock or DC braking.
Closed
The drive is outputting frequency
OFF
ON
OFF
OFF
ON
ON
Run
command
Baseblock
command
Output
frequency
During frequency
output
Figure 6.60 During Frequency Output Operation
36: Drive Enabled
Shows the status of multi-function terminal input E1-□□= 69 (Drive Enabled). When the input
terminal E1-□□= 69 is closed, the output terminal closes as well.
37: Watt Hour Pulse Output
Outputs a pulse to indicate the watt hours. Refer to E2-05 (Output Power Detection Scaling )
for details.
38 : Local/Remote Mode
The output terminal closes in Local mode and opens in Remote mode.
Terminal
Description
Open
Remote: The frequency and Run command can be provided by the external device
selected by b1-00/b1-01 or b1-07/b1-08.
Closed
Local: The frequency and Run command can be provided by the drive keypad.
39 : During Speed Search
The assigned output terminal closes during Speed Search. Refer to b3 (Speed Search) for
details.
40 :PID Feedback Low