4.3.1 Control Circuit Terminals
4.3.1.1 Control circuit input and output terminal (<5.5kW (more) models )
Table 4.3.1.1 Control Circuit Input Terminal
Terminal Type
Terminal
Code
Terminal Name
Terminal Description
Multi-Function
Digital Inputs
S1
Digital input terminal 1 (forward/stop)
Photocoupler, 24 V / 8 mA.
Use Sink / Source switch to select
multi-function digital input type.
The default is Sink mode.
S2
Digital input terminal 2 (reverse/stop)
S3
Digital input terminal 3 (external fault signal
1)
S4
Digital input terminal 4 (Jog command)
In addition to the characteristic S1
~ S3, but also for the high-speed
pulse input channel.
Maximum input frequency: 50KHz
High voltage: 10 ~ 24V
Low voltage: 0 ~ 0.5V
For digital inputs, switch Sink /