101
determined by the C1-09 (Acc./Dec. Time Unit Selection) setting. When C1-09 = 0, the setting range is 0.00 to
600.00 (second).
C1-11/ C1-12 Jog Frequency Acc. / Dec. Time
C1-11 sets the acceleration time from 0Hz to the Jog frequency command (L1-16). And C1-12
sets the deceleration time from the Jog frequency command (L1-16) to 0Hz.
No.
Name
Setting Range
Default
C1-11
Jog Frequency Acc. Time
0.0 to 6000.0 s <1>
10.0 s
C1-12
Jog Frequency Dec. Time
<1> The setting range changes depending on the C1-09 setting. When C1-09 = 0 (Units of 0.01s), the range will be
0.00s to 600.00s.
C2 S-Curve Characteristics
Sets the S-curve characteristics to reduce the shock to the machinery at start and stop. Sets the
S-curve characteristic time at the start and stop of acceleration and deceleration.
C2- 00 to C2- 03 S-Curve Characteristic at Start/Stop of Acc./Dec.
Sets the S-curve characteristic time in C2-00 to C2-03.
No.
Name
Setting Range
Default
C2-00
S-Curve Characteristic
at Acc. Start
0.00 to 10.00 s
0.20 s
C2-01
S-Curve Characteristic
at Acc. End
C2-02
S-Curve Characteristic
at Dec. Start
C2-03
S-Curve Characteristic
at Dec. End
S-curve characteristics are illustrated below.