
97
6.3 Group C, Tuning
C1
Acceleration and Deceleration Time
C1- 00 to C1- 07 Acceleration and Deceleration Times 1 to 4
Four different acceleration and deceleration times can be set in the drive by multi-function
input terminals, motor selection or switched during run.
Set the acceleration time to determine the time needed to accelerate from 0Hz to the
maximum frequency (d1-02). Set the deceleration time to determine the time needed to
decelerate from the maximum frequency (d1-02) to 0Hz.
C1-00 and C1-01 are the active acceleration and deceleration times by default.
No.
Name
Setting Range
Default
C1-00
Acceleration Time 1
0.0 to 6000.0 s <1>
10.0 s
C1-01
Deceleration Time 1
C1-02
Acceleration Time 2
C1-03
Deceleration Time 2
C1-04
Acceleration Time 3
(Acceleration Time 1 for Motor 2)
C1-05
Deceleration Time 3
(Deceleration Time 1 for Motor 2)
C1-06
Acceleration Time 4
(Acceleration Time 2 for Motor 2)
C1-07
Deceleration Time 4
(Deceleration Time 2 for Motor 2)
<1> The setting range of Acc./Dec is changed according to the setting of C1-09 (Acc./Dec. Time Unit Selection).
When C1-09 = 0 (0.01 second), then the setting range is 0.00 to 600.00 (s).
□ Switching Acceleration Times by Multi-Function Input
C1-00 and C1-01 are the active acceleration and deceleration times by default. Enable C1-02
to C1-07 by E1-□□ (Multi-Function Digital Inputs)= 16 (Acc./Dec. Time Selection 1) and
17(Acc./Dec. Time Selection 2). Refer to Table 6.9.
Table 6.9 Acc./Dec. Times Selection by Multi-Function Input
Acc./Dec. Time Selection 1
E1-□□= 16
Acc./Dec Time Selection 2
E1-□□= 17
Active Times
Acceleration
Deceleration
Summary of Contents for EVO 6800 Series
Page 1: ...MANUAL Compact Vector Drive EVO 6800 Series...
Page 33: ...33 34 2 36 0 2 8 93 0...
Page 35: ...35 4 2 Main Circuit...
Page 41: ...41 4 3 Control Circuit...