62
Chapter 6
│
Parameters
6.1 Group A, Initialization
Sets the initial parameters (group A parameter) such as Access Level Selection, password and
etc.
A1 Initialization
A1- 00 Retain
A1- 01 Access Level Selection
Selects access level (edit/ view)
No.
Name
Setting Range
Default
A1-01
Access Level Selection
0, 1, 2
2
0 : View Only
Access to only parameter A1-01
1 : User-Defined Parameter Access
Access to only parameter A1-01 and A2-00 to A2-31
2 : All Parameter Access
All parameters can be edited and viewed
Note:
·
Once the password is set to A1-05, user cannot edit A1-01, A1-03, A1-06, A2-01 to A2-32 before entering the
correct password in A1-04.
·
Once E1-□□= 60 (Program Lockout) is set, user cannot edit any parameters before closing the assigned
terminal, even when A1-01 = 1 or 2.
·
When using Modbus communication to edit parameters, it is not possible to edit parameters via keypad until
an ENTER command is given to the drive from the communication.
A1- 02 Control Method Selection
No.
Name
Setting Range
Default
A1-02
Control Method Selection
0 to 1
0