200
in t1-02 and t1-04, this parameter will automatically display the no-load current of a standard
motor. The no-load current must be entered according to the motor test report.
No.
Name
Setting Range
Default
t1-09
Motor No-Load Current
(Stationary Auto-Tuning)
0.0 A to (t1-04)( Max
∶
0 to 2999.9)
-
1.
Note: The maximum motor rating the drive can run changes depending on the A1-06 (ND/HD Selection)
setting. Refer to Ch 2.4 on page 15.
t1-10
Retain
t1-11
Retain
t1-12
Motor Auto-Tuning Setting
Enables or disables Auto-Tuning when A1-02=0 to 3.
No.
Name
Setting Range
Default
t1-12
Motor Auto-Tuning Setting
0,1
0
0: Disabled
1: Enabled
Enables the motor Auto-Tuning. Set t1-12 to 1 and press the ENTER key to switch the display
to the motor Auto-Tuning preparation (tUnxx). The last two letters changes depending on the
selected motor (motor 1 or 2) and t1-01 setting.
Press the MENU key to cancel Auto-Tuning and leave this display or press the RUN key to start
the motor Auto-Tuning function.
The display flashes in process and shows “End” after Auto-Tuning is completed. If
Auto-Tuning fails, the process stops immediately and shows “tnFxx” on the screen which
“xx” indicates the problems. Refer to Chapter 8.4 Auto-Tuning for more details.
When the Auto-Tuning function is required to be controlled by the keypad, set b1-01(Run
Command Selection 1) to 0 (Keypad). Otherwise Auto-Tuning cannot be started by pressing
the RUN key.
.