6.11 Group U, Monitor Settings
U parameters views the data concerning drive operation.
Parameter Name
Description
Unit
Group U, Monitor Settings
U1: Status Monitors
U1-00
Control Method
0: V/F Control
1: SVVCl
-
U1-01
Frequency
Command
Displays the frequency command. (Display units are defined
by o1-00)
-
U1-02
Output Frequency
Displays the output frequency. (Display units are defined by
o1-00)
-
U1-03
Output Current
Displays output current.
0.01A
U1-04
Motor Speed
Displays the motor speed.
-
U1-05
Output
Voltage
Command
Displays the drive output voltage command.
0.1V
U1-06
Main
Circuit
DC
Voltage
Displays the main circuit DC voltage.
0.1V
U1-07
Output Power
Displays the internal output power calculated by the drive.
0.001kW
U1-09
Input Terminal Status
Displays the status of the input terminal.
U1-09=C11111111:
The following indicate each digit from right to left.
1:Digital Input 1 (S1 enabled )
1:Digital Input 2 (S2 enabled )
1:Digital Input 3 (S3 enabled )
1:Digital Input 4 (S4 enabled )
1:Digital Input 5 (S5 enabled )
1:Digital Input 6 (S6 enabled )
1:Digital Input 7 (S7 enabled )
-
U1-10
Output
Terminal
Status
Displays the status of the output terminal.
U1-10=o1111:
The following indicate each digit from right to left.
Multi-Function Terminal Output (terminal R1A/R1B-R1C)
-