197
Keeps track of time when the output voltage is active.
o4-02 Cooling Fan Operation Time Setting
Sets the initial value to start keeping track of cumulative fan operation time. View the
cumulative fan operation time in U3-01. Reset this value to 0 after the fan replacement.
Note:
1. Set this value in units of 10 h. A setting of 20 will set the cumulative operation time to 200h and the monitor will
display 300h in U3-00.
2. The cooling fan may require maintenance at an earlier date in harsher environments.
No.
Name
Setting Range
Default
o4-02
Cooling Fan Operation Time Setting
0 to 6000 h
0h
o4-03 to o4-05
Retain
o4-06
U2 Reset Setting
Resets the data for U2-□□ (Fault Information) as this data will not be reset by A1-03 (Reset).
No.
Name
Setting Range
Default
o4-06
U2 Reset Setting
0,1
0
0 : No Action
The data for the U2-□□ (Fault Information) monitor will not be reset.
1 : Enabled
Resets the data for the U2-□□ (Fault Information) monitor. Set this value to 1 and press ENTER
will clear all the fault information to 0.
o4- 07 kWh Monitor Initialization
Manually resets kWh monitors U3-08 and U3-09. Initializing the drive or cycling the power will
not reset these monitors.
No.
Name
Setting Range
Default
o4-07
kWh Monitor Initialization
0,1
0
0 :No Action
The kWh data (U3-08、 U3-09) are maintained
1 :Reset kWh Data
Resets the kWh counter. The monitors U3-08 and U3-09 will display “0” after they are
initialized. Setting o4-07 to 1 and pressing the ENTER erases kWh data and returns the display