38
shipped from the factory with a short-circuit jumper. Remove the jumper before
connecting a DC reactor.
+1
+2
(DC+)
DC Reactor (option)
If the drive is used in a high-frequency or heavy duty application which requires frequent
braking or shorter deceleration time, install an optional braking resistor to increase the
braking torque.
B1
B2
Braking Resistor (option)
Please refer to the wiring diagram when installing braking options.
4.2.2.4 Ground Terminal
Use grounding cables of dimensions regulated by electrical equipment standard. Shrink
wiring distance to prevent leakage current resulting unstable electrical potential at the
terminal distant from grounding terminal.
Do not use share the same grounding cable with welding machines or any device
requiring large current. Failure to comply could cause drive or equipment malfunction.
Do not wind the grounding cable when multiple drives are installed. Failure to comply
could cause drive or equipment malfunction.
Ensure the neutral of the input side and drive terminal "
“ are grounded
according to the local electrician regulations. 3WYE (e.g. TN and TT) system are
suggested for the drive primary side.
4.2.2.5 Jumper:
EVO8000 complies with the European LVD standard EN 61800-5-1 (2007) reducing the
current leakage to below 10mA DC under testing condition regulated by IEC 60990
(1999).
Follow the instructions below to remove the jumper if an even lower current leakage to a