117
Power
supply
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
ON
L4-01 = 1
L4-01 = 0
Hold
Hold
Forward
Run/ Stop
Hold
Acc./Dec.
Frequency
Command
Output
Frequency
Figure 6.40 Frequency Command Hold with Acc./Dec. Hold
·
Up/Down and Up/Down 2
The frequency command will be saved when the Run command is removed, and remain active
when the drive restarts. To reset the saved frequency command to 0 Hz, enter UP or DOWN
before entering a Run command.
L6 Offset Frequency
L6- 00 to L6- 02 Offset Frequency 1 to 3
Sets the offset value as a percentage of the maximum output frequency to add to or subtract
from the frequency command. Select the offset frequency in E1-□□= 53, 54 and 55 (Offset
Frequency 1 to 3). The offset frequency will not add up being minus value and run in a reverse
direction as it is limited by the upper and lower limit.
No.
Name
Setting Range
Default
L6-00
Offset Frequency 1
-100.0 to 100.0%
0.0%
L6-01
Offset Frequency 2
-100.0 to 100.0%
0.0%
L6-02
Offset Frequency 3
-100.0 to 100.0%
0.0%