143
Open
Run command is provided from external command 1 (b1-01) or 2 (b1-08)
Closed
Run command is provided from the drive keypad.
11 : Fault
When a fault is triggered, the assigned output terminal closes.
12 : Communication Mode
If the terminal is assigned to 12, it can be the output terminal for the upper controller using
Modbus communication. If the signal is not set by the upper controller, the signal will not
perform any action.
13 : Alarm
When an alarm such as PID Feedback High (FBH), PID Feedback Low (FBL) or Overcurrent (HCA)
is triggered, the assigned output terminal closes.
14 : Fault Restart
When attempting to reset a fault from the control circuit terminals, via serial communications,
the assigned output terminal closes.
15 : Timer Output
Sets a output terminal as the output for the timer function. Refer to b4 (Timer Function).
16 : Frequency (FOUT) Detection 1
When the output frequency exceeds the P4-00 (Frequency Detection Level) level plus the
P4-01 (Frequency Detection Width) level, the assigned output terminal closes until the output
frequency reaches the P4-00 level.
Terminal
Description
Open
The output frequency exceeds the P4-00 level plus the P4-01 level
Closed
The output frequency does not exceed the P4-00 level plus the P4-01 level
Note:
1. The detection and the P4-00 level work in both forward and reverse directions.
2. It will be the motor speed when using Closed-Loop Vector Control.
Frequency
detection 1
OFF
ON
Output
frequency
P4-00
P4-01
P4-01
P4-00