182
The drive continues to run at the frequency set to P4-03 during frequency command loss.
When the frequency command is restored, the operation will be continued with the frequency
command.
P4-03
Frequency Command at Frequency Command Loss
Sets the frequency command level at which the drive runs when detecting a frequency
command loss and when L4-02 is set to 1. Sets the value as a percentage of the maximum
output frequency set in d1-02. (Sets the value as a percentage of the motor 2 maximum output
frequency set in d1-13.)
No.
Name
Setting Range
Default
P4-03
Frequency Command at Frequency Command
Loss
0.0 to 100.0%
80.0 %
P4-04
Frequency Command Loss Detection Time
When the frequency command falls below 90% of the command within this detection time, the
frequency command loss will be detected.
No.
Name
Setting Range
Default
P4-04
Frequency Command Loss Detection Time
20 to 400ms
20ms
P4-05
Brake control release frequency
No.
Name
Setting Range
Default
P4-05
Brake control release frequency
0.00 ~ 20.00Hz
0.00Hz
P4-06 Brake control action frequency
No.
Name
Setting Range
Default
P4-06
Brake control action frequency
0.00 ~ 20.00Hz
0.00Hz
P5 Fault Restart
Fault Restart tries to automatically restart the motor and continue operation to prevent the
motor from stopping when a fault is detected.
The drive diagnoses itself and continues operation when a fault is detected during run. If the
self-diagnosis is successful to clear the fault, the drive restarts automatically with Speed Search.
Refer to b3 (Speed Search) for details.
Note:
1. The Run command (forward/ reverse) will automatically be removed when the sequency control circuit makes the
fault shut off the drive output.
2. When the Run command is removed, the drive diagnoses itself, attemps to clear the fault and restart.