183
WARNING! Do not perform Fault Restart in applications such as lifting, which could cause the machine to drop the
load.
Fault Restart can be performed when the following faults occur.
Fault
Fault Name
Fault
Fault Name
GF
Ground Fault
OL2
Drive Overload
OVA
Overvoltage (Acceleration)
Ot1
Overload Detection 1
OVD
Overvoltage (Deceleration)
Ot2
Overload Detection 2
OVC
Overvoltage (Constant Speed)
PF
Input Phase Loss
oCA
Overcurrent (Acceleration)
LF1
Output Phase Loss
oCD
Overcurrent (Deceleration)
oCC
Overcurrent (Constant Speed)
OH
Heatsink Overheat
OL1
Motor Overload
Set Fault Restart in P5-00 to P5-03.
Set E2-00 to E2-03 to 14 (Fault Start) to output the signal to an external devices.
P5-00
Number of Auto Restart Attempts
Sets the number of times to automatically attempt to restart the drive when detecting the fault
listed above. The drive will stop operation when the restart attemps reach the number set in
this parameter. Clear the cause of the fault manually and restart the drive.
The number of auto restart attemps is reset to 0 in the following situations.
·
The drive runs normally for 10 minutes after a fault restart.
·
A fault is reset manually after the protection function is triggered.
·
The power supply is cycled.
No.
Name
Setting Range
Default
P5-00
Number of Auto Restart Attempts
0 to 10
0
P5- 01 Auto Restart Fault Output Operation
Enables or disables the fault output via E2-□□= 11 (Fault) during Fault Restart.
No.
Name
Setting Range
Default
P5-01
Auto Restart Fault Output Operation
0, 1
0
0 : Fault Output Disabled
1 : Fault Output Enabled
P5-02
Fault Restart Interval Time
Sets the amount of time between restart attempts.