91
PID Sleep
PID Sleep operation is illustrated below.
PID Output
b5-14 PID Sleep
Start Level
Sleep Delay Time
Sleep Delay
Time
b5-15
b5-15
Run Command Enabled
Continues to Output “During Run”
Internal Run
Command
External Run
Command
During Run
Run
Stop
Figure 6.20 PID Sleep Operation
Notes for PID Sleep function
·
The Stopping Method for PID Sleep function is determined by b1-02
·
Set the PID Sleep function in b5-14 and b5-15.
b5- 14 PID Sleep Start Level
Sets the frequency level used to trigger PID Sleep.
PID Sleep will be triggered when the PID output or frequency command falls below the level
set to b5-14 for the time longer than the time set to b5-15. The drive will resume operation
when the PID output or frequency command exceeds the level set to b5-14 for longer than the
time set in b5-15.
No.
Name
Setting Range
Default
b5-14
PID Sleep Start Level
0.0 Hz to <1>
0.0 Hz
<1> The upper limit is determined by the values set to d1-02 (Maximum Output Frequency), d1-13 (Motor 2
Maximum Output Frequency) and L2-00 (Frequency Command Upper Limit).
b5- 15 PID Sleep Delay Time
Sets the delay time used to activate/deactivate the PID Sleep function,
If b5-15 is set to 0.0s,
the PID sleep function does not operate
No.
Name
Setting Range
Default
b5-15
PID Sleep Delay Time
0.0 to 25.5 s
0.0 s
b5- 16 PID Acc./Dec. Time