Run command
Output frequency
Motor speed
b2-01 DC Braking current
Motor coasts
P2-01 Minimum
baseblock time
DC Braking time
Figure 6.6 DC Braking to Stop
DC Braking time is determined by b2-03 (DC Braking Time at Stop) and the output frequency
when a Stop command was entered.
DC Braking time = (b2-03)×10×Output frequency / d1-02(Maximum output frequency)
DC Braking time
b2-03 * 10
b2-03
10%
100%
Max. output frequency
Output frequency at the time a
Stop command is given
Figure 6.7 DC Braking Time Depending on Output Frequency
Note: If an OCD (Overcurrent) fault occurs, increase the minimum baseblock time to P2-01.
3 : Coast to Stop with Timer
When a Stop command is given, the drive shuts off its output and the motor will coast to stop.
The drive will ignore any Run command until the wait time (t) ends.