68
A1
0 to 10 V
E3-00 = 0
E3-01 = 0
(Main Frequency Command)
E3-02 E3-03
-10 to 10 V E3-00 = 1
A2
0 to 10 V
E3-06 = 2
E3-07 = 0
(Main Frequency Command)
E3-08 E3-09
Ensure DIP switch A2 is
placed to V (voltage)
0 to 5 V
E3-06 = 3
+V
AC Drive
A1
Main frequency command
(voltage input)
A2 Main frequency command
(voltage/current input)
AC
-V
Analog input common
-10V,20mA power supply
10V,20mA power supply
2kΩ
0 to 10V
4kΩ
+V
AC Drive
A1
A2
AC
-V
-10 to 10V
10V,20mA power supply
Main frequency command
(voltage input)
Main frequency command
(voltage/current input)
Analog input common
-10V,20mA power supply
Figure 6.1 Setting Frequency Command as a Voltage Signal at Terminal A1
Wire all the analog input terminals according to Figure 6.1. Ensure DIP switch A2 is placed to
V (voltage).
□ Current Input
Allows a voltage input via terminal A2. Refer to Table 6.5 for parameter settings.
Table 6.5 Frequency Command Using Current Signals
Terminal Signal Level
Parameter Settings
Notes
Signal Level
Selection
Function
Selection
Gain
Bias
A2
0 to 20 mA E3-06 = 0
E3-07 = 0
E3-08
E3-09
Ensure DIP switch A2 is
placed to I (current)
4 to 20 mA E3-06 = 1