219
Keypad
Display
Fault Name
Cause
Possible Solution
2. Check possible solution to
suppress the noise
CF
Retain
Err
Retain
Sto
Retain
JoGEr
FJOG/ RJOG Input
Error
A FJOG and RJOG Run
commands are received at
the same time
Check the Run command from
the external source for Fjog/Rjog
8.3 Operation Errors
Table 8.3 Error Displays, Causes, and Possible Solutions
Keypad
Display
Error Name
Cause
Possible Solution
oPE02
Parameter Range
Setting Error
Parameters are set outside of
the possible setting range
1.
Set the parameters to the
proper values
2.
Reset the drive
oPE03
Multi-Function
Input Selection
Error
1. Either of Up command and
Down command is not set
(
E1-□□=
10 or 11 )
2. Either of Up command 2
and Down command 2 is not
set (
E1-□□=
12 or 13)
Properly assign both of the UP and
Down commands to the
multi-function input terminal.
oPE04
3-Wire
Sequence
Control
Setting
Error
Multi-Function input
terminals S1 and S2 are
assigned to
E1-□□=
2 (3-Wire
Sequence)
Do not assign multi-function input
terminals S1 and S2 to E1-□□= 2
(3-Wire Seq
uence)
oPE05
Communication
Error
oPE06
Control Method
Selection Error
A control method that
requires a PG option card
(A1-02 = 1, 3, or 5) is
selected, but no PG card is
installed
Install a PG option card or correct
the value set to A1-02
oPE07
Multi-Function
Analog Input
E3-01 and E3-07 are set to
the same value
Set different values to E3-01 and
E3-07
Summary of Contents for EVO 6800 Series
Page 1: ...MANUAL Compact Vector Drive EVO 6800 Series...
Page 33: ...33 34 2 36 0 2 8 93 0...
Page 35: ...35 4 2 Main Circuit...
Page 41: ...41 4 3 Control Circuit...