224
9.2 Periodic Inspection
Perform regular inspections according to the following check lists to ensure the optimum
product performance and status.
9.2.1 Environment
Inspection Points
Corrective Action
Inspection Cycle
Daily
6
months
12
months
Ambient
temperature,
humidity,
vibration, dusk, harmful gases, oil mist,
water.
Eliminate the source of contaminants or
correct poor environment.
○
Any foreign material or tool left
around?
Eliminate foreign material or tool.
○
9.2.2 Voltage
Inspection Points
Corrective Action
Inspection Cycle
Daily
6
months
12
months
Is the DC bus and control circuit voltge
normal?
Correct the voltage or power supply to
within nameplate specifications.
Verify all main circuit phases.
○
9.2.3 Keypad Monitor
Inspection Points
Corrective Action
Inspection Cycle
Daily
6
months
12
months
Is the display clear to see?
Clean the keypad monitor.
○
Any character missing?
Contact the local Lite-On distributor.
○
9.2.4 Enclosure
Inspection Points
Corrective Action
Inspection Cycle
Daily
6
months
12
months
Are the screws all tightened?
Replace the damaged screws or
terminals if tightening is not possible.
○
Is the shape changed?
Replace the damaged components
Replace the entire drive if necessary.
○