111
Output
Frequency
Frequency Command
Upper Limit
Frequency Command
Lower Limit
Frequency
Command
Operating
Range
L2-00
L2-01
Figure 6.36 Frequency Command Upper and Lower Limits
L3 Jump Frequency
L3-00 to L3-03
Jump Frequency 1 to 3 / Jump Frequency Range
Sets the Jump frequency range to avoid operation at the speed causing resonance in the
machinery. If the frequency command falls within a Jump frequency range, the drive will hold
the frequency command at the upper limit of the range until accelerating past this range when
the frequency command rises above that upper limit.
Sets L3-00 to L3-02 to 0.0 Hz to disable Jump frequency.
No.
Name
Setting Range
Default
L3-00
Jump Frequency 1
0.0 Hz to <1>
0.0 Hz <2>
L3-01
Jump Frequency 2
L3-02
Jump Frequency 3
L3-03
Jump Frequency Range
0.0 to d1-02 <3>
1.0 Hz <3>
<1> The upper limit is determined by the values set to d1-02 (Maximum Output Frequency), d1-13 (Motor 2
Maximum Output Frequency) and L2-00 (Frequency Command Upper Limit).
<2> In PM Closed-Loop Vector Control, the setting range is 0.0 to 100.0% and the default setting is 0.0% .
<3> In PM Closed-Loop Vector Control, the setting range is 0.0 to 40.0% and the default setting is 1.0% .
The relationship between the output frequency and the Jump frequency is illustrated in the
following figure.