136
terminal will disable it. PID control remains active when the terminal is open.
47 : PID Integral Reset
Resets the PID control integral value to 0 when closing the input terminal. Refer to
48 : PID Integral Hold
Holds the PID integral value when the input terminal is closed, and restarts PID integral when
the terminal is open. Refer to Fig 6.16?
49 : PID Soft-Start On/Off
Disables b5-16 (PID Command Acc./Dec. Time) when the input terminal is closed and enables
it when the terminal is open. Refer to Fig 6.16?
50 : PID Input Characteristics Switch
Switches the PID input characteristics. Refer to Fig 6.16?
51 : Retain
52 : Timer Input
Use this setting combination with E2-□□=15 (Timer Output). Refer to b4 (Timer Function) for
details.
53/54/55 : Offset Frequency 1/ 2/ 3
Adds offset frequencies L6-00 to L6-02 to the frequency command when the terminal is closed.
Refer to L6-00 to L6-02 (Offset Frequency 1/ 2/ 3).
56 : Retain
57: KEB Command 1
Enables or disables KEB Command 1. When KEB Command 1 is enabled, selects KEB method
from P2-09 = 0 to 2.
Drive Operation
Multi-Function Terminal Input
Setting (Normal Closed)
Setting (Normal Open)
KEB Function
Open
Closed
Normal Operation
Closed
Open
58:Retain
Summary of Contents for EVO 6800 Series
Page 1: ...MANUAL Compact Vector Drive EVO 6800 Series...
Page 33: ...33 34 2 36 0 2 8 93 0...
Page 35: ...35 4 2 Main Circuit...
Page 41: ...41 4 3 Control Circuit...