0 : V/F Control
This method is recommended for those applications without the need of fast response,
accurate speed control. Select this method also when using a single drive to run more than
one motors, the motor parameters are unknown or Auto-Tuning cannot be performed. The
speed control range is 1 : 40.
1 : SVVC
A1-03
Reset
Resets parameter settings to default settings. After resetting parameters, the value will
automatically set to 0.
No.
Name
Setting Range
Default
A1-03
Reset
0 to 9999
0
0: N/A
2538: Resets 2-Wire Sequence/ 50Hz / 380V
2541: Resets 2-Wire Sequence / 50Hz / 415V
2544: Resets 2-Wire Sequence / 50Hz / 440V
2546: Resets 2-Wire Sequence / 50Hz / 460V
2638: Resets 2-Wire Sequence / 60Hz / 380V
2641: Resets 2-Wire Sequence / 60Hz / 415V
2644: Resets 2-Wire Sequence / 60Hz / 440V
2646: Resets 2-Wire Sequence / 60Hz / 460V
3538: Resets 3-Wire Sequence / 50Hz / 380V
3541: Resets 3-Wire Sequence / 50Hz / 415V
3544: Resets 3-Wire Sequence / 50Hz / 440V
3546: Resets 3-Wire Sequence / 50Hz / 460V
3646: Resets 3-Wire Sequence / 60Hz / 460V
Note:
The parameter listed in Table 6.1 will not be reset when setting 2220 or 3330 to A1-03.