164
E5-09 Average PWM Signal Times
The drive averages the PWM signal for the set times to be an more stable frequency command.
If it is set to 5 times, the drive then averages the continuous 5 PWM signals as the frequency
command. The more times it is set, the more stable the frequency command will be. But the
response of the frequency command will be slower at the same time.
No.
Name
Setting Range
Default
E5-09
Average PWM Signal Times
1 to 100
1
E5-10 PWM Signal Cycle
Sets the PWM signal cycle. The tolerance is about ±12.5%.
No.
Name
Setting Range
Default
E5-10
PWM Signal Cycle
1 to 999 ms
100 ms
E6
Optional Communication Card Settings
E6-00 to E6-05
Retain
E6-06
Drive Station Address
No.
Name
Setting Range
Default
E6-06
Drive Station Address
1 to 31
1
E6-07
RS-485 Communication Speed Selection
No.
Name
Setting Range
Default
E6-07
RS-485 Communication Speed Selection
0 to 8
3
0: 1200 bps (bit/sec)
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6 : 57600 bps
7 : 76800 bps
8 : 115200 bps
E6-08
RS-485 Communication Parity Selection
No.
Name
Setting Range
Default
Summary of Contents for EVO 6800 Series
Page 1: ...MANUAL Compact Vector Drive EVO 6800 Series...
Page 33: ...33 34 2 36 0 2 8 93 0...
Page 35: ...35 4 2 Main Circuit...
Page 41: ...41 4 3 Control Circuit...