Versiv Series Cabling Certification Product Family
Technical Reference Handbook
342
GPU22.EPS
Figure 143. EventMap Example 2
Length of the tail cord (top) and launch cord (bottom).
A non-reflective loss event:
: An APC connector or a splice. Measurements for the event
are all within the test limits. If the event has negative loss, it is a
Gainer
. See page 351.
If
Macrobend Detection
is
Off
, this could be a bend. If the event
is a bend, and
Macrobend Detection
is
On
, the EventMap shows
the bend icon. Macrobend detection is available only for
singlemode fibers.
: One or more measurements for the event exceeds the limit.
A
C
A
B
D
E
F
Summary of Contents for CableAnalyzer DSX-5000
Page 24: ...xxii Versiv Series Cabling Certification Product Family Technical Reference Handbook...
Page 34: ...xxxii Versiv Series Cabling Certification Product Family Technical Reference Handbook...
Page 220: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 184...
Page 268: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 232...
Page 330: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 294...
Page 338: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 302...
Page 592: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 556...
Page 604: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 568...
Page 620: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 584...
Page 672: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 636...
Page 676: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 640...
Page 688: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 652...