Versiv Series Cabling Certification Product Family
Technical Reference Handbook
312
Table 12. Settings for OTDR Tests
Module
Select the OptiFiber Pro module you will use.
To select a different module, tap the
Module
panel on the
TEST SETUP
screen, then tap a module.
Test Type
When you turn on the tester, the
Test Type
shows the test
that was last selected.
Auto OTDR
: The tester automatically selects settings that
give you the best view of the events on the cabling. This
mode is the easiest to use and is the best choice for most
applications. To see the settings the tester used for an
Auto OTDR
test, tap
SETTINGS
on the trace screen.
Note
Some unusual faults can cause the Auto OTDR test
to show an unsatisfactory trace. If this occurs, use
the Manual OTDR test to get a better trace.
Manual OTDR
: This mode lets you select settings to control
the test parameters for the trace. See “The SmartLoop
Test” on page 376 for details.
DataCenter OTDR
: This test is optimized for fiber
installations that have short links, many connections, and
the possibility of large reflections. The maximum range for
this test is 1.2 km for multimode and 5 km for singlemode.
For more details on DataCenter OTDR settings, see
“OptiFiber Pro DataCenter OTDR Specifications” on page
625.
Notes
By default, the DataCenter OTDR test uses 850 nm
for multimode fiber and 1310 nm for singlemode
fiber. These are the wavelengths typically used in
data centers. You can select other wavelengths if
necessary. If you use only one wavelength, the
Macrobend Detection function will not identify
bends.
You must use launch compensation when you do
a DataCenter OTDR test.
-continued-
Summary of Contents for CableAnalyzer DSX-5000
Page 24: ...xxii Versiv Series Cabling Certification Product Family Technical Reference Handbook...
Page 34: ...xxxii Versiv Series Cabling Certification Product Family Technical Reference Handbook...
Page 220: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 184...
Page 268: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 232...
Page 330: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 294...
Page 338: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 302...
Page 592: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 556...
Page 604: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 568...
Page 620: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 584...
Page 672: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 636...
Page 676: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 640...
Page 688: ...Versiv Series Cabling Certification Product Family Technical Reference Handbook 652...