Wiring Closet Considerations
Be aware of the following recommendations for your wiring closet:
●
Be sure that your system is easily accessible for installation and service. See
“Rack Specifications and
Recommendations” on page 27
for information.
●
Use appropriate AC power, power distribution, and grounding for your specific installation.
●
Use a vinyl floor covering in your wiring closet. (Concrete floors accumulate dust, and carpets can
cause static electricity.)
●
Prevent unauthorized access to wiring closets by providing door locks. Install the equipment in a
secured, enclosed, and restricted access location, ensuring that only qualified service personnel have
access to the equipment.
●
Provide adequate overhead lighting for easy maintenance.
●
Be sure that each wiring closet has a suitable ground. All distribution racks and equipment installed
in the closet should be grounded.
●
Be sure that all system environmental requirements are met, such as ambient temperature and
humidity.
NOTE
Extreme Networks recommends that you consult an electrical contractor for commercial building and wiring
specifications.
Temperature
Extreme Networks equipment generates a significant amount of heat. It is essential that you provide a
temperature-controlled environment for both performance and safety.
Install the equipment only in a temperature- and humidity-controlled indoor area that is free of airborne
materials that can conduct electricity. Too much humidity can cause a fire. Too little humidity can
produce electrical shock and fire.
Follow these general thermal recommendations for your wiring closet:
●
Be sure that the ventilation in the wiring closet is adequate to maintain a temperature below 104° F
(40° C).
●
Install a reliable air conditioning and ventilation system.
●
Keep the ventilation in the wiring closet running during non-business hours; otherwise, the
equipment can overheat.
●
Maintain ambient operating temperature: 32° to 104° F (0° to 40° C).
●
Maintain storage temperature: -40° to 158° F (-40° to 70° C).
NOTE
Like all electrical equipment, product lifetimes degrade with increased temperature. If possible, temperatures should
be kept at approximately 78
°
F (25
°
C) or lower.
Summary of Contents for BlackDiamond 10808
Page 14: ...Table of Contents Extreme Networks Consolidated ExtremeXOS Hardware Installation Guide 14 ...
Page 18: ...Preface Extreme Networks Consolidated ExtremeXOS Hardware Installation Guide 18 ...
Page 19: ...1 Site Preparation ...
Page 20: ......
Page 40: ...Site Preparation Extreme Networks Consolidated ExtremeXOS Hardware Installation Guide 40 ...
Page 41: ...2 BlackDiamond Switches ...
Page 42: ......
Page 93: ...3 Installing BlackDiamond Switches and Modules ...
Page 94: ......
Page 189: ...4 Installing BlackDiamond Switch Accessories ...
Page 190: ......
Page 207: ...5 BlackDiamond Maintenance Procedures ...
Page 208: ......
Page 239: ...6 Summit Family of Switches ...
Page 240: ......
Page 335: ...7 Optics ...
Page 336: ......
Page 363: ...8 Initial Management Access ...
Page 364: ......
Page 369: ...9 Appendixes ...
Page 370: ......